XGN15 (DXG) -12 indoor AC high-voltage-type sulfur ring in order to counter the new generation of sulfur hexafluoride load switch as the main switch and the entire cabinet air insulation for power distribution automation, not only compact but also expansion of the metal-enclosed switchgear. XGN15-12 small-scale switching of fixed equipment, is the CEC Longyuan Electric Power Company of the Commonwealth by the State organization commissioned a joint design of a new generation of small-scale urban and rural power equipment, with high-grade, small size, parameters of the whole, low-cost, less maintenance and so on. The ring counter has a simple structure, flexible operation, reliable interlocking characteristics of a variety of applications, different users are able to provide satisfactory solutions. The latest sensor technology and the use of protection relays, together with the advanced technical performance and the Light of Hope Live assembly program, you can fully satisfy the requirements of the ever-changing market. This series of ring counters following IEC standards: IEC60298 metal exchanges closed distribution devices and control equipment (1kV-52kV) (1990), Am1 (1994) IEC60694 specifications commonly used high-voltage switchgear and control equipment (1996) IEC60044-1 the first part of Instrument Transformers Current Transformer IEC60044-2 the second part of induction instrument transformer voltage transformer IEC60056 general exchange of high-voltage line switch IEC60129 general exchange of isolation switches and earthing switches (1984) Am1 (1992) Am2 (1996) IEC60256-1 the first part of high-voltage switches (1kV-52kV) (1998) IEC60420 general exchange of load switch - fuse combinations (1990) Switchgear IEC60529 provides protection level (IP standard) This series of ring counters of the following national standards: GB 3906 3 ~ 35kV AC metal-enclosed switchgear GB/T11022 high voltage switch equipment and control equipment to share the technical requirements of standards The exchange of high-voltage load switch GB/T16926 - fuse combinations GB 3804 3 ~ 63kV AC high voltage load switch Inside of the electrical components are in line with their respective standards. Ring counters for three-phase AC 50Hz, rated voltage of 12kV indoor switchgear. Widely used in industrial and civil cable ring network and power supply terminal. Especially suitable for small-scale secondary distribution points, opening and closing, the industrial and mining enterprises, urban districts, airports, railways, tunnels, power systems, such as high-rise building as a receiving and distribution of electric energy use. Ring counters closed metal sheathed, insulated air inside. Connection with a terminal substation and adapt to the wire loop power supply. This series of ring counter equipment specification parts used: selection of circuit breakers (vacuum or SF6 type), grounding switches, fuses, instrument transformers, the secondary instrument, through a combination of these components to a broad range of design options to meet the requirements. According to the needs of low-voltage boxes can be created. Products are reliable mechanical interlock devices to meet the "five-anti" functional requirements. The main switch can be selected: DLF-12 sulfur hexafluoride load switch, FLN36-12D-type sulfur hexafluoride load switch, vacuum circuit breakers, etc.; ABB companies can also choose SFL-12/24 original sulfur hexafluoride load-type switch, HAD / us-based or sulfur hexafluoride circuit breaker VD4-S-type, such as vacuum circuit breakers.
■ Technical parameters □ Switchgear rated load parameters of the earth switch rated peak current tolerance
ID
|
Name |
Units |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Main busbar rated current |
A |
630 |
3 |
Rated Current |
A |
630 |
4 |
Rated Frequency |
Hz |
50 |
5 |
Rated current short-term tolerance |
kA |
20 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated peak current tolerance |
kA |
50 |
8 |
Rated short-circuit closing current |
kA |
50 |
9 |
Rated active load breaking current |
A |
630 |
10 |
Rated breaking current of the closed-loop |
A |
630 |
11 |
Rated cable charging breaking current |
A |
10 |
12 |
Short-term tolerance of the earth switch rated current |
kA |
20 |
13 |
Grounding switch rated short-circuit duration |
s |
4 |
14 |
Grounding switch rated peak current tolerance |
kA |
50 |
15 |
Rated insulation level |
1min power frequency tolerance voltage (RMS) |
kV |
(White, relative to) 42; (fracture) 48 |
Lightning Impulse Voltage tolerance (peak) |
kV |
White, relative to) 75; (fracture) 85 |
16
|
Main circuit resistance |
μΩ |
≤400 |
17 |
Mechanical life |
Load switch |
Times |
5000 |
Earthing switch |
Times |
2000 |
18 |
1min auxiliary circuit voltage frequency tolerance |
kV |
2 |
19 |
SF 6 gas rated pressure (20 ℃ gauge) |
MP a |
0.04 |
20 |
SF 6 gas leakage rate in |
|
1% |
21 |
Protection level |
|
IP3X |
□ Portfolio of rated parameters of electrical cabinets
ID |
Name |
Units |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated Frequency |
Hz |
50 |
3 |
Rated Current |
A |
125* |
4 |
Rated short-circuit breaking current |
kA |
31.5* |
5 |
Rated short-circuit closing current |
kA |
80 |
6 |
Rated transfer current |
A |
1700 |
7 |
Main circuit resistance (without fuse) |
μΩ |
≤400 |
8 |
Rated insulation level |
1min power frequency tolerance voltage (RMS) |
kV |
(White, relative to) 42; (fracture) 48 |
Lightning Impulse Voltage tolerance (peak) |
kV |
(White, relative to) 75; (fracture) 85 |
9 |
Mechanical life |
Load switch |
次 |
5000 |
Earthing switch |
次 |
2000 |
10 |
1min auxiliary circuit voltage frequency tolerance |
kV |
2 |
11 |
SF 6 gas rated pressure (20 ℃ gauge) |
MP a |
0.04 |
12 |
SF 6 gas leakage rate in |
|
1% |
13 |
Protection level |
|
IP3X | |